SPECIFICATIONS
Brand Name: APNEU
Type: Earth Leakage
is_customized: Yes
Is Smart Device: No
Certification: CE
Model Number: TVPS1-63C
1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
7. Voltage calibration: Voltage +-10% adjustable. A13
8. Current calibration: Current +- 9/5% adjustable A15
9. Restore factory settings: press the down button for more than 12s
10.Fault inquiry: Press the UP button from more than 12S
Product Parameters:
1.Model number:TVPS1-63
2.Power supply:230VAC 50/60Hz
3.Max.Loading power: 1~40A Adjustable(default:20A)
1~63A Adjustable(default:40A)
1~80A Adjustable( default:60A)
4.Over-voltage protection value range:230V~300~OFF(default:270V)
Over-voltage recovery voltage range:225V--295V(default:250V)
Over-voltage protection action time:0.1s~30s(default value:1s)
Over-voltage r ecovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:140V--210V --OFF(default:170V)
Under-voltage recovery voltage range:145V--215V (default:190V)
Under-voltage protection action time:0.1s~30s(default:1s)
Under-voltage r ecovery delay time:1s~500s(default:30s)
6.Over-current adjustment range:1-40A (default:20A) 1-63A (default:40A) 1-80A(default:60A)
Over-current action range:0.1~30 second (default:1s)
Over-current r ecovery delay time:1s~500s(default:30s)
7.Power-on delay time:1s~500s(default:10s)
8.Power consumption : <2W
9.Electric machinery life : 100,000 times
10.Installation:35mm DIN rail
110V Version
1.Model number:TVPS1-63C
2.Power supply:110VAC 50/60Hz
3.Max.Loading power:1~63A Adjustable(default:40A)
4.Over-voltage protection value range:80V~300~OFF(default:145V)
Over-voltage recovery voltage range:75V--295V(default:140V)
Over-voltage protection action time:0.1s~30s(default value:1s)
Over-voltage recovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:80V--300V --OFF(default:90V)
Under-voltage recovery voltage range:85V--305V (default:95V)
Under-voltage protection action time:0.1s~30s(default:1s)
Under-voltage recovery delay time:1s~500s(default:30s)
6.Over-current adjustment range:1-63A (default:40A)
Over-current action range:0.1~30 second (default:1s)
Over-current recovery delay time:1s~500s(default:30s)
7.Power-on delay time:1s~500s(default:10s)
8.Power consumption : <2W
9.Electric machinery life : 100,000 times
10.Installation:35mm DIN rail